Transformer Oil X has been developed and formulated to provide strong resistance to oil degradation.Provide excellent oxidation stability for a longer transformer life requiring less maintenance.
This product has been developed for use in oil-filled electrical equipment, especially power and distribution transformers, rectifiers, circuit breakers and switches.
Kinematic Viscosity, 40°C, mm2/s |
ISO 3104 |
Max 12.0 |
|
Kinematic Viscosity, -30°C, mm2/s |
ISO 3104 |
Max 1800 |
|
Pour Point, °C |
ISO 3016 |
Max -40 |
|
Water content, mg/kg |
IEC 60814 |
Max 30 |
|
Fault Voltage |
Before the repair, kV |
IEC 60156 |
Min 30 |
After the repair, kV |
IEC 60296 |
Min 70 |
|
Density ,20°C, kg/dm3 |
ISO 12185 |
Max 0,895 |
|
DDF, 90°C |
IEC 60247 |
Max 0,005 |
|
Appearance |
IEC 60296 |
Clear and no sediment |
|
TAN, mg KOH/g |
IEC 62021 |
Max 0,01 |
|
Interfacial Tension, mN/m |
EN 14210 |
Min 40 |
|
Total Sulfur Content, % |
ISO 14596 |
Max 0,05 |
|
Corrosive Sulfur |
DIN 51353 |
Not abrasive |
|
Potentially Corrosive Sulfur |
IEC 62535 |
Not abrasive |
|
Corrosive Sulfur |
ASTM D 1275 B |
Not abrasive |
|
DBDS, mg/kg |
IEC 62697-1 |
Undetermined |
|
Antioxidant, %W |
IEC 60666 |
0,08-0,4 |
|
Metal Content |
IEC 60666 |
Undetermined |
|
2- The Contents of Furfural and Related Compounds |
IEC 61198 |
Undetermined |
|
Aromatic Content |
IEC 60590 |
5 |
|
Oxidation Stability (120°C,500h) |
TAN, mg KOH/g |
IEC 61125 C |
0,3 |
Mud, %W |
Max 0,05 |
||
DDF (90°C) |
Max 0,05 |
||
Flash Point, °C |
ISO 2719 |
Min 135 |
|
PCA, %W |
IP 346 |
Max 3 |
|
PCB |
IEC 61619 |
Undetermined |
* Data given above are typical properties and may vary slightly.
IEC 60296 Edition 4.0, passes corrosion tester: ASTM D1275 method B, IEC 62535, DIN 51353
MARCH 2018 REV01